EV Charger Requirements in Europe and the UK: Type 2, CCS2, Protection, Metering and Public Charging Rules

EV charger rules for Europe and the UK: supply and earthing, Type 2 and CCS2, IEC 61851, 6 mA DC and PEN protection, MID, AFIR and UK regulations.

Prepared by
VULTAE Engineering Team
Published
Reading time
5 min
Sources
8 references

At a glance

Supply
230 V 1-phase / 400 V 3-phase, 50 Hz
AC connector
Type 2 (IEC 62196-2)
DC connector
CCS2 (IEC 62196-3)
Product standards
IEC 61851-1 · -21-2 · -23
AC protection
RCD Type A + 6 mA DC, or Type B
Billing meters
MID; Eichrecht in Germany
EU public charging
AFIR (Reg. 2023/1804)
UK
Smart Charge Points Regs 2021 · Public Charge Point Regs 2023

Key takeaways

  1. 1European chargers run on 230 V single-phase or 400 V three-phase at 50 Hz and use Type 2 for AC and CCS2 for DC. Check the earthing system: TN is most common, TT occurs in rural areas, and many Norwegian homes use IT networks that need compatible chargers.
  2. 2Each AC connection point needs residual-current protection that also detects DC fault currents — a Type A RCD with a 6 mA DC detecting device (IEC 62955) or a Type B RCD — under IEC 60364-7-722 and national wiring rules.
  3. 3In the UK, charge points on PME supplies need protection against an open PEN fault (BS 7671), private charge points must meet the Smart Charge Points Regulations 2021, and public ones the Public Charge Point Regulations 2023.
  4. 4Public chargers in the EU must meet AFIR — ad-hoc card payment and price display at 50 kW and above — and billing meters may need MID approval or, in Germany, Eichrecht-compliant metering.
Slim on-street charge points on the pavement of a British terraced street, one charging an electric car with a Type 2 cable
Slim on-street charge points on the pavement of a British terraced street, one charging an electric car with a Type 2 cable
Contents
  1. 01Supply and earthing
  2. 02Connectors and charging modes
  3. 03Protection: RCD, 6 mA DC detection and PEN faults
  4. 04Metering and billing
  5. 05Public charging in the EU: AFIR
  6. 06United Kingdom
  7. 07VULTAE IEC versions

Short answer: a charger for Europe or the UK must suit 230 V single-phase or 400 V three-phase 50 Hz supplies and the local earthing system; use Type 2 for AC and CCS2 for DC; be tested to IEC 61851-1 (and -23 for DC) with EMC to IEC 61851-21-2; protect each AC connection point against AC and 6 mA DC fault currents; in the UK, handle PEN faults and meet the Smart Charge Points or Public Charge Point regulations; and, for public charging in the EU, meet AFIR and local metering law such as MID or Germany’s Eichrecht.

Supply and earthing

Supply Typical chargers Earthing to check
230 V single-phase, 32 A 7.4 kW wallboxes TN-C-S (PME in the UK) — PEN fault protection needed in the UK
400 V three-phase, 16 A 11 kW wallboxes TN-S / TN-C-S; TT in many rural areas
400 V three-phase, 32 A 22 kW wallboxes and AC pedestals As above
400 V three-phase, 63 A and above DC chargers Usually a dedicated supply or substation
230 V three-phase IT networks Common in Norwegian homes Charger must be approved for IT networks

Three-phase supplies are widespread in continental Europe; many UK homes have single-phase supplies only, which limits home charging to about 7 kW.

Connectors and charging modes

Use Connector Mode
Home and workplace AC Type 2 socket or tethered Type 2 cable Mode 3
Public AC posts Type 2 sockets (driver’s own cable) Mode 3
DC fast charging CCS2 (Combo 2) Mode 4
Legacy DC CHAdeMO on some older sites Mode 4
Portable charging cable Type 2 vehicle connector, domestic or industrial plug Mode 2

Protection: RCD, 6 mA DC detection and PEN faults

Two accepted ways to protect an AC charging point against residual currents Option 1: Type A RCD 30 mA plus a residual direct current detecting device that disconnects at 6 mA DC, often built into the charger. Option 2: Type B RCD 30 mA, which detects smooth DC residual currents itself. UK PME supplies additionally need PEN fault protection. OPTION 1OPTION 2 RCD Type A30 mA AC + RDC-DD (IEC 62955)6 mA DC, in the charger Lower cost; most wallboxes integrate the 6 mA DCdetection, so a standard Type A RCD is enough upstream. RCD Type B30 mA AC + smooth DC Detects DC residual currents itself; moreexpensive, used where the charger has no DC detection. UK PME supplies: add PEN fault protection (BS 7671) — built into the charger or by an earth electrode arrangement.
Every AC connection point needs protection against both AC and DC residual currents. A Type A RCD plus 6 mA DC detection in the charger is the most common combination.

IEC 60364-7-722 — implemented in national wiring rules such as BS 7671 in the UK and VDE 0100-722 in Germany — requires each AC connection point to have its own overcurrent protection and residual-current protection that responds to DC fault currents above 6 mA. Most modern wallboxes build in the 6 mA DC detection (RDC-DD to IEC 62955), so the installer can fit a standard Type A RCD upstream. In the UK, charge points on PME supplies also need protection against an open PEN conductor, which many UK-market wallboxes build in.

Metering and billing

Rule Where What it means for the charger
MID (2014/32/EU), active energy meters EU member states that regulate billing meters MID-approved meter for kWh billing
Eichrecht Germany Approved metering with verifiable, signed readings; transparency software for drivers
National rules Other countries Check local metrology requirements for public billing

Public charging in the EU: AFIR

The Alternative Fuels Infrastructure Regulation (Regulation (EU) 2023/1804) applies across the EU from April 2024 and sets requirements for publicly accessible charging:

Requirement Summary
Ad-hoc payment Charging without a subscription; points of 50 kW and above deployed from April 2024 need a card reader or contactless card-reading device; DC points on the core TEN-T network must be retrofitted by 2027
Price display Price per kWh shown at points of 50 kW and above; clearly available for lower-power points
Connectivity New public points digitally connected and capable of smart charging
Network targets On the core TEN-T, a fast-charging pool every 60 km per direction: at least 400 kW per pool with one 150 kW point by end-2025, rising to 600 kW with two 150 kW points by end-2027

United Kingdom

Rule Applies to Key points
Electric Vehicles (Smart Charge Points) Regulations 2021 Private charge points sold in Great Britain Smart functionality, default off-peak charging, randomised delay of up to 10 minutes, measuring system, security consistent with ETSI EN 303 645
Public Charge Point Regulations 2023 Public charge points Contactless payment on new points of 8 kW and above and on rapid points; 99 % reliability for rapid networks; staffed 24/7 helpline; open data via OCPI
BS 7671, section 722 Installation Dedicated circuits, RCD and DC fault protection, PEN fault protection on PME
UKCA or CE Product marking CE recognised indefinitely in Great Britain for these product types

VULTAE IEC versions

VT-HW wallbox VT-CW / VT-CP dual-port VT-DW / VT-DFC / VT-DF DC
Supply 230 V 1-phase or 400 V 3-phase, 50/60 Hz 230 / 400 V 230 / 400 V 3-phase
Output 3.7, 7.4, 11, 22 kW 2 × 3.7–22 kW 20–300 kW
Connector Type 2 socket (shutter option) or tethered Type 2 CCS2; CHAdeMO option
Protection Type A 30 mA + 6 mA DC; PEN fault option (UK) IP55 · IK10; MID-certified meter option IP54 · IK10
Back end OCPP 1.6J / 2.0.1 OCPP 1.6J / 2.0.1 OCPP 1.6J / 2.0.1

IEC versions are supplied with CE, UKCA and TÜV certification; we send the certificates and test reports for the exact model you order. See importing chargers into the EU and UK for the documents and registrations.

Questions buyers ask

What connector do EV chargers use in Europe?
Type 2 (IEC 62196-2) for AC charging and CCS2 (IEC 62196-3, Combo 2) for DC fast charging. Public AC chargers usually have Type 2 sockets so drivers use their own cable; home wallboxes are often tethered. CHAdeMO is a legacy option on some older DC sites.
Does an EV charger need a Type B RCD in Europe?
Not necessarily. IEC 60364-7-722 and national wiring rules require each AC connection point to be protected against DC fault currents as well as AC residual currents. That can be a Type B RCD, or a Type A RCD combined with a residual direct current detecting device (RDC-DD) to IEC 62955 that trips at 6 mA DC — often built into the charger.
What is PEN fault protection in UK chargers?
On PME (TN-C-S) supplies, a broken PEN conductor can make the vehicle body dangerous to touch. BS 7671 requires charge points on PME supplies to be protected, typically by a device in the charger that detects abnormal voltage and disconnects all conductors, or by an earth electrode arrangement.
Do European public chargers need a card reader?
Under AFIR, publicly accessible charging points of 50 kW and above deployed since April 2024 must accept ad-hoc payment with a payment card reader or a contactless device that reads cards, and DC points on the core TEN-T network must be retrofitted by 2027. Lower-power points may use other secure methods such as a QR code.
What is Eichrecht?
German calibration law. Public chargers that bill by energy must use approved metering whose readings customers can verify, usually with signed meter values and transparency software. Many operators in Germany only buy Eichrecht-compliant models.

References

  1. [1]IEC 61851-1:2017 — general requirements. International Electrotechnical Commission.
  2. [2]IEC 62955:2018 — residual direct current detecting device (RDC-DD) for mode 3 charging. International Electrotechnical Commission.
  3. [3]IEC 60364-7-722:2018 — supplies for electric vehicles. International Electrotechnical Commission.
  4. [4]Regulation (EU) 2023/1804 on alternative fuels infrastructure (AFIR). EUR-Lex.
  5. [5]AFIR — EU policy update. ICCT.
  6. [6]Measuring Instruments Directive 2014/32/EU. EUR-Lex.
  7. [7]Regulations: electric vehicle smart charge points. GOV.UK.
  8. [8]Public Charge Point Regulations 2023 guidance. GOV.UK.